GOV-BOARD
Gov-Board assemblies up to and including 6 lineal feet are shipped in one piece. Longer assemblies are shipped in two or more pieces or sub-assemblies, none of which exceeds 6 lineal feet.
Narrow trim lines (2-1/2" wide) allows unit to blend with any decor. This unit can take the place of the base molding and can be painted to match your walls.
The Gov-Board unit with its unique integral cast design offers high efficiency and maximum output. Your Guarantee of performance.
I=B=R Rating Data
Notes
|
I=B=R Rating Data
| Flow Rate |
Steam Rate |
*Water Ratings BTUH Per Linear Foot at Average Water Temp. Indicated |
| Lbs/Hr |
Sq. Ft. |
BTU/Hr at 215° F |
170° F |
180° F |
190° F |
200° F |
210° F |
220° F |
230° F |
| 500 |
3.15 |
750 |
490 |
550 |
610 |
680 |
740 |
800 |
870 |
| 2000 |
3.15 |
750 |
520 |
580 |
640 |
720 |
780 |
850 |
920 |
I=B=R Ratings are determined from test made in accordance with the I=B=R Testing and Rating Code for baseboard type radiation, including an allowance of 15% for heating effect permitted by the code.
"Pressure drop Ratings are available for all sizes directly from Governale Company, Inc."
Notes
- The Hot Water Ratings at 2000 lb. flow rate are limited to installations where the water flow rate through the GOV-BOARD is equal to or greater than 2000 lbs per hour (4 GPM)
- Where the water flow rate through the GOV-BOARD is not know, the rating at the standard flow rate of 500 lbs. (1 GPM) per hour must be used.
- Rating based on active length. Active length same as total length.
- Maximum allowable working pressure - 30 PSI, Water: 15 PSI, steam.